Installation design and maintenance of steam heater in bathhouse

The steam heater in the bathhouse can be used for all the occasions where the steam is used to prepare domestic hot water, such as: the shower system in the bathhouse, the hotel spa system, the preparation of domestic hot water, etc. The steam heater in the bathhouse can meet the needs of thousands of showers. It is ideal for factory bathhouses and large hotel baths. wholesale shower steamers to talk about steam heater installation design and maintenance.

1. The steam heater in the bathroom is a flange interface. The steam pipe is connected to the water tank (pool) and connected with a flange. During installation, the bottom of the heater should be about 200mm from the bottom of the tank, and the water should be ensured to flood the mixer more than 100mm.

2. When selecting the type, the diameter of the pipeline should be greater than or equal to the nominal diameter of the heater. When multiple heaters are used in parallel, the cross-sectional area of the steam pipeline should be greater than or equal to the sum of the cross-sectional area of all the heaters connecting pipes.

3. The check valve must be installed near the heater on the steam pipe road to prevent the siphon phenomenon when the steam stops, leading to the occurrence of water backflow accidents. When the steam pressure is greater than 0.5MPa (gauge pressure), the steam pressure reducing valve should be installed to decompress, and the filter should be installed before it.

4. The steam heater in the bathroom and bathhouse is used in parallel and should be evenly distributed. Because of its large weight, it should be supported. The steam pipe near the heater should be firmly fixed, so that it will not swing when working.

5. The water temperature and water level of the water tank should be measured and controlled by temperature controller and water level controller.

6. Maintenance and maintenance of the steam heater in the bathroom: if the heating speed is found to be moderate in the process of using the heater, it may be that the internal steam hole is blocked. The heater should be removed to remove the impurities that are blocked in the steam hole, and the dirt should be discharged from the sewage outlet.